12
No. Item code Item
Factory default
User Settings and descriptions
settings
settings
29 C 29
Selections available when power
00:Continues until power is turned off.
is on during PV channel switching
1:PV1
2:PV2
3:High-temperature PV
4:Low-temperature PV
30 C 30 PV equalizer 0 0 : Not provided
1:PV1 only
2:PV2 only
3:Both PV1 and PV2
31 C 31 End of operation 0 0 : READY mode
1:END mode
32 C 32
Manipulated variable in READY mode
0.0 –5.0 to +105.0%
33 C 33 Manipulated variable setting 0 0 : Not provided
in PV overrange 1 : Provided
34 C 34 Manipulated variable in PV 0.0 –5.0 to +105.0%
overrange
35 C 35 MANUAL change mode 0 0 : Smooth
1:Preset
36 C 36 Preset MANUAL value 0.0 –5.0 to +105.0%
43 C 43 Service interruption time when 0 0 to 3600sec
running can be continued
45 C 45 Auxiliary output 1 type 0 0 : SP
1:PV
2:Deviation (DEV)
3:Manipulated variable (MV)
4:PV1
5:PV2
46 C 46
Auxiliary output 1 lower limit (4mA)
0 SPU –19999 to +20000 SPU (C45 not equal to 3)
–1999.9 to +2000.0% (C45 set to 3)
47 C 47
Auxiliary output 1 upper limit (20mA)
10000 SPU –19999 to +20000 SPU (C45 not equal to 3)
–1999.9 to +2000.0% (C45 set to 3)
48 C 48 Auxiliary output 2 type 0 0 : SP
1:PV
2:Deviation (DEV)
3:Manipulated variable (MV)
4:PV1
5:PV2
49 C 49
Auxiliary output 2 lower limit (4mA)
0 SPU –19999 to +20000 SPU (C48 not equal to 3)
–1999.9 to +2000.0% (C48 set to 3)
50 C 50
Auxiliary output 2 upper limit (20mA)
10000 SPU –19999 to +20000 SPU (C48 not equal to 3)
–1999.9 to +2000.0% (C48 set to 3)
52 C 52 SP output lower limit (4mA) 0 SPU –19999 to +20000 SPU
53 C 53 SP output upper limit (20mA) 10000 SPU –19999 to +20000 SPU
57 C 57 Programming item 0 0 : Displayed
Event 1 : Not displayed
58 C 58 Programming item 0 0 : Displayed
PID group, output limiter group 1 : Not displayed
59 C 59 Programming item 0 0 : Displayed
G.SOAK, PV shift, repeat 1 : Not displayed
60 C 60 Programming item 0 0 : Displayed
PV start, cycle, pattern link 1: Not displayed
61 C 61 Programming system 0 0 : RAMP-X and RAMP-T (θ) combined
1:RAMP-X and RAMP-E (SP) combined
62 C 62 Program time unit 0 0 : Hours, min (SPU/hour for RAMP-T)
1:Min, sec (SPU/min for RAMP-T)
2:0.1 sec (SPU/sec for RAMP-T)
63 C 63
Time display (display panel 2)
00:Remaining segment time
1:total operation time (after READY RUN start)
65 C 65 SP decimal point position 1 0 to 4
DCP551 Parameter Work Sheet
denotes items settable only on models with two PV input channels.