5-4
NOTE
Select the program pattern setting system using setup data setting C61.
0: combined use of RAMP-X and RAMP-T
1: combined use of RAMP-X and RAMP-E
Select time setting units using setup data setting C62.
0: hours and minutes
1: minutes and seconds
2: 0.1 seconds
Select θ setting units using setup data setting C62.
0: SPU/hour
1: SPU/min
2: SPU/sec
Select SP setting and SP setting decimal position using setup data setting C65.
0: XXXXX
1: XXXX.X
2: XXX.XX
3: XX.XXX
4: X.XXXX
External switch for pulse input requires 1: RAMP-E using a setup data setting
between C71 to C74.
The pulse input interval time can be checked by setting event type 93 in the
event. Event type 93 is RAMP-E time monitored during a period of 0.0 to
3000.0 seconds.
Even when a setting is exceeded and there is no pulse input, the event remains
on.