When working with a text codepad, go to Menu 833 [Write adapter] to copy the control panel
memory to the DLA.
Command 963 - Copy IUI-SOL-ADAPTER data to the Control Panel
This command copies data from the direct link adapter to the control panel. You can only use
the IUI-SOL-ADAPTER Direct Link Adapter only with the control panel.
To copy the direct link adapter memory to the control panel:
1. Enter the Installer Code (the default is 1234) and press [#] to enter Installer’s
Programming Mode. Two beeps sound and the STAY and AWAY indicators flash on the
codepad to indicate you entered Installer’s Programming Mode. The codepad displays the
data stored in Location 000.
2. Connect the direct link adapter to the Bosch SDI2 Bus pins at the bottom of the control
panel printed circuit board.
3. Enter [9 6 3 #]. Two beeps sound after the direct link adapter’s data is successfully
copied to the control panel. A long beep indicates that the direct link adapter is corrupt
and must be erased to clear the corrupt data.
4. Enter [9 6 0 #] to exit from Installer’s Programming Mode. The STAY and AWAY indicators
are extinguished on the codepad to indicate the system is disarmed.
5. Remove the direct link adapter from the control panel Failure to exit from Installer’s
Programming Mode before removing the direct link adapter can corrupt the direct link
adapter.
When working with a text codepad, go to Menu 832 [Read adapter] to copy the DLA data to
the control panel.
Command 965 - Set up Domestic Dialing Format
Command 965 simplifies the setup of the domestic dialing format to a one-step operation.
Refer to Domestic Dialing, page 79 for more information.
To set up domestic dialing format:
1. Enter the Installer Code (the default is 1234) and press [#] to enter Installer’s
Programming Mode. Two beeps sound and the STAY and AWAY indicators flash on the
codepad to indicate you entered Installer’s Programming Mode. If on a text codepad, go
to menu 81 [Address Program]. The codepad displays the data Mode. The codepad
displays the data stored in Location 000.
2. Enter [9 6 5 #]. The command automatically sets Receiver 1 to domestic reporting and
sets other locations or Receiver 2 only (refer to the table Command 965 Defaults below).
No other locations are changed when you issue command 965.
3. If on a text codepad, enter the Installer Code (the default is (1234) and press [#] to enter
Installer’s Programming Mode. Go to menu 747 [Set Up Domestic Dialing Format], then
save and exit.
The transmission format is automatically set for domestic dialing and the Subscriber ID
Number set for one identification beep. All reports, except Zone Status reporting and System
Status reporting, are allocated to Receiver 1 for domestic dialing.
Zone Status Reports including Zone Bypass, Zone Trouble, Sensor Watch, and Alarm Restore
codes, and System Status Reports including AUX Power Supply Fail, AC Fail, Low Battery, and
Access Denied Reports are allocated to Receiver 2 and do not report unless Receiver 2 is also
set up to report.
5.1.6
5.1.7
Control Panel Configuration | en 27
Bosch Security Systems, Inc. Installation Guide 2017.10 | 03 | F.01U.298.026

Table of Contents

Other manuals for Bosch Solution 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Solution 2000 and is the answer not in the manual?

Bosch Solution 2000 Specifications

General IconGeneral
Zones8
Expandable ZonesUp to 16
Event Log100 events
Partitions2
Battery BackupYes
Weight2.5kg
Backup Battery12V 7Ah
Arming OptionsStay, Away
CommunicationPSTN (optional IP module)

Related product manuals