Page #39 background imageLoading...
Page #39 background image
Indicator FAULT description
3 RF receiver fault
This fault registers when the RF wireless receiver unit detects RF jamming, the
RF wireless receiver is disconnected from the control panel or failed, or the RF
receiver’s cover tamper switch is activated.
4 Warning Device fault
This fault registers when the system detects output 1-3 as warning device
(Horn Speaker, Siren Running, Strobe) is disconnected or short. This fault
clears once all outputs are reconnected. This feature is enabled by selecting
Option 2 in Location 492 (refer to System Options 1, page 138).
5 Telephone line fault
This fault registers when the system detects the telephone line is disconnected
from the control panel. This feature is enabled by selecting Option 1 in
Location 176.
7 Power Supply fail
This fault occurs when AUX power supplies fail, +12V power fails, or SDI2 Bus
power fails. Contact your installer as soon as this fault displays.
8 Onboard Tamper
This fault occurs when the system detects the control panel is tampered.
9-16 RF Repeater Tamper/Fail
The RF repeater 1 to 8 fault registers once the system detects that the wireless
repeater is disconnected or the repeater tamper is triggered.
AC MAINS Failure
An AC MAINS supply failure automatically flashes the MAINS indicator. If the AC MAINS supply
is disconnected continuously for longer than 2 min, the remote codepad beeps the codepad
buzzer once per min. If the control panel is programmed to report an AC MAINS failure to a
base station receiver, an AC Fail Report (Contact ID Event Code 301) is transmitted.
The MAINS indicator stops flashing when the AC MAINS supply is reconnected. When the AC
MAINS supply is connected continuously for 2 min, the codepad stops the once per min beep
and an AC Fail Restore Report is transmitted to the base station receiver.
If the Enable AC Fail in 1 Hour option (1) is selected in Location 494 (refer to System Options
3, page 139), the codepad flashes the MAINS indicator when the AC MAINS supply is
disconnected, but does not activate the report or the codepad buzzer unless the AC MAINS
supply is disconnected continuously for 1 hour.
If the Ignore AC MAINS Fail option (2) is selected in Location 494 (refer to System Options 3,
page 139) the codepad does not indicate when the AC MAINS supply fails, but the control
panel still reports an AC Fail Report, if enabled.
Inquire cloud status
You can inquire cloud status only with the alphanumeric codepad IUI-SOL-TEXT.
When the control panel is connected to the cloud module B4xx-M, go to menu 721 Network
Module to select B4xx-M and set it to enable.
Inquire the cloud status to check connection status to the cloud service and to view the
module UID.
6.14
Control Panel System Operations | en 39
Bosch Security Systems, Inc. Installation Guide 2017.10 | 03 | F.01U.298.026

Table of Contents

Other manuals for Bosch Solution 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Solution 2000 and is the answer not in the manual?

Bosch Solution 2000 Specifications

General IconGeneral
Zones8
Expandable ZonesUp to 16
Event Log100 events
Partitions2
Battery BackupYes
Weight2.5kg
Backup Battery12V 7Ah
Arming OptionsStay, Away
CommunicationPSTN (optional IP module)