position controller Type 8692
4.3.5 SPLTRNG
Signal split range
Min. and max. values of the input signal as % for which the valve runs through the entire stroke range.
Factory setting: Min = 0 %; Max = 100 %
This function is effective only during operation as a position controller.
Use this auxiliary function to limit the position set-point value range of the positioner by specifying a minimum and a maximum
value. As a result, it is possible to divide a utilised unit signal range (4 – 20 mA, 0 – 20 mA, 0 – 10 V or 0 – 5 V) into several
positioners (without or with overlapping). This allows several valves to be used alternately or in the case of overlapping set-
point value ranges simultaneously as actuators.
SPLTRNG
Min 0 %
Max 100 %
EXIT
ENTER
INPUT
+
-
Min 0 %
OK
INPUT
+
-
Max 100 %
OK
*
*
Input the minimum value of
the input signal as %
Adjustment range:
0 ... 75 %
Input the maximum value of
the input signal as %
Adjustment range:
25 ... 100 %
Fig. 21: Operating structure SPLTRNG
Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.
Splitting a unit signal range into two set-point value ranges
Valve stroke [%]
(POS)
Set-point value [mA]
(INP)
Set-point value range
Position controller 1
Set-point value range
Position controller 2
Fig. 22: Graph SPLTRNG
* If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.