CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Module temperature
reached
When the A0.60(AC drive temperature) is greater than or equal to
Eb.27(Module temperature reaches the set value), the terminal output
ON signal.
Motor Over heat
pre-warning
When A0.59(The temperature of the motor) is greater than or equal to
F0.14(Motor overheat warning threshold), the terminal output ON
signal.
When the AC drive output current is less than Eb.17(Zero current
detection level), and duration is reached to Eb.18(Zero current
detection delay time) set value, the terminal output ON signal
Please refer to the E7.05(Set count value) parameters.
Designated count value
reached
Please refer to the E7.06(Designated count value) parameters.
Please refer to the E7.07(Set length) parameters.
Accumulative power-on
time reached
When A0.54(Accumulative power on time(day)) + A0.55(Accumulative
power on time(hour)) equals to Eb.04(Accumulative power-on
time(day) threshold) + Eb.05(Accumulative power-on time(hour)
threshold), the terminal output ON signal. If Eb.04(Accumulative
power-on time(day) threshold) is set to 0, the cumulative power on
timing function is disabled, and output OFF signal.
Accumulative running
time reached
When A0.56(Accumulative running time(day)) + A0.57(Accumulative
running time(hour)) equals to Eb.06(Accumulative running time(day)
threshold) + Eb.07(Accumulative running time(hour) threshold), the
terminal output ON signal. If Eb.06(Accumulative running time(day)
threshold) is set to 0, the cumulative power on timing function is
disabled, and output OFF signal.
Current running time
reached
When A0.53(Running time)reaches to the set value of Eb.03(Current
running time reached)the terminal output ON signal
Reference to Eb.09(Any frequency reaching detection value 1)and
Eb.10(Any frequency reaching detection amplitude 1)parameter’s
description
Reference to Eb.11(Any frequency reaching detection value 2)and
Eb.12(Any frequency reaching detection amplitude 2)parameter’s
description
Reference to Eb.21(Any current reaching 1)and Eb.22(Any current
reaching 1 amplitude)parameter’s description
Reference to Eb.23(Any current reaching 2)and Eb.24(Any current
reaching 2 amplitude)parameter’s description
Reference to F0.09(Under load protection)and F0.10
(Detection level of under load)parameter’s description