CDE360 Vector Control AC Drive Chapter 5 Parameter List Table
-66-
Function
Code
Name
Range
Default
Step
Description
d3.13
Dynamic torque
compensation
0.0~100.0
0.0
0.1%
d3.14
Inertia torque
compensation
0.0~100.0
0.0
0.1%
d3.15
Torque acceleration time
0.00~650.00
2.00
0.01Sec
d3.16
Torque deceleration
time
0.00~650.00
2.00
0.01Sec
d3.17
Maximum torque
reference
-300.0~300.0
150.0
0.1%
d3.18
Minimum torque
reference
-300.0~300.0
-150.0
0.1%
d3.17~d3.18 is the limit of torque reference under torque control mode,and is also the maximum setting
value when AI, FI and Communication input.
d5 Motor 2 Parameters
Function
Code
Name
Range
Default
Step
Description
d5.00
Motor 1/2 selection
0~1
0
1
0: Motor 1
1: Motor 2
d5.01
Motor 2 control mode
0~2
0
1
0: V/f
1: Open loop vector control
2: Close loop vector control
d5.03
Motor 2 rated power
0.1~999.9
Module
dependent
0.1kw
d5.04
Motor 2 rated voltage
1~2000
1V
d5.05
Motor 2 rated current
0.01~655.35
0.01A
d5.06
Motor 2 rated frequency
10.00~b0.00
0.01Hz
d5.07
Motor 2 rated speed
1~65535
1RPM
d5.08
Motor 2 stator
resistance
Module
dependent
Module
dependent
0.001ohm
d5.09
Motor 2 rotor resistance
0.001ohm
d5.10
Motor 2 leakage
inductance
0.01mH
d5.11
Motor 2 mutual
inductance
0.1mH
d5.12
Motor 2 No-load current
0.01A
d5.13
Motor 2 weaken flux
coefficient 1
0.000~1.000
1.000
0.001
Flux weakening
coefficient at 20%
flux current