CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Group L0: Communication Setting
Set the baud rate for RS485 communication.
0: 4800 bits/s
1: 9600 bits/s
2: 19200 bits/s
3: 38400 bits/s
4: 57600 bits/s
Set the data format for RS485 communication.
0: 8 data bit, no check, 1 stop bit<8,N,1>
1: 8 data bit, no check, 2 stop bit <8,N,2>
2: 8 data bit, even parity check, 1 stop bit<8,E,1>
3: 8 data bit, odd parity check, 1 stop bit <8,O,1>
Set the drive communication address.
The slave address of zero is broadcast address, the address of 1~247 are
usable.
The interval from receiving data to replying data to the master.
Communication
timeout detection
Set L0.04 to zero, the communication timeout function is invalid.
Set L0.04 to non-zero, if the interval time between twice communication
exceed L0.04, the AC drive will display “Er31”(RS485 communication
fault)