CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Group L0: Communication Setting
L0.00
Range: 0~4
Default: 1
Baud rate
Set the baud rate for RS485 communication.
0: 4800 bits/s
1: 9600 bits/s
2: 19200 bits/s
3: 38400 bits/s
4: 57600 bits/s
L0.01
Range: 0~3
Default: 1
Data format
Set the data format for RS485 communication.
0: 8 data bit, no check, 1 stop bit<8,N,1>
1: 8 data bit, no check, 2 stop bit <8,N,2>
2: 8 data bit, even parity check, 1 stop bit<8,E,1>
3: 8 data bit, odd parity check, 1 stop bit <8,O,1>
L0.02
Range: 1~247
Default: 1
Slave address
Set the drive communication address.
The slave address of zero is broadcast address, the address of 1~247 are
usable.
L0.03
Range: 0~20
Default: 2
Response delay
Unit: mSec
The interval from receiving data to replying data to the master.
L0.04
Range: 0.0~60.0
Default: 0.0
Communication
timeout detection
Unit: Sec
Set L0.04 to zero, the communication timeout function is invalid.
Set L0.04 to non-zero, if the interval time between twice communication
exceed L0.04, the AC drive will display “Er31”(RS485 communication
fault)