CDE360 Vector Control AC Drive Chapter 6 Parameters Description
0: Ramp stop 1: Coasting stop
When set E0.04 to 1,the AC drive will response the JOG command of
current control source immediately even if in running state.And the JOG
command form other control source will be ignored.
0: Disabled 1: Enabled
Group E1: Skip Frequency
If the set frequency is within the frequency jump range, the actual running frequency is the skip
frequency close to the set frequency. Setting the skip frequency helps to avoid the mechanical
resonance point of the load.
The AC drive supports two skip frequencies. If both are set to 0, the skip frequency function
is disabled.
Skip frequency
1 high limit
As shown in the following figure.
Skip frequency 1
low limit
As shown in the following figure.
Skip frequency 2
high limit
As shown in the following figure.
Skip frequency 2
low limit
As shown in the following figure.
Note: The AC drive can output in the skip frequency range during acceleration and
deceleration process.
The principle of the skip frequencies is shown in the following figure.
输出频率Hz
时间t
跳跃频率2
跳跃频率1
跳跃频率幅度
跳跃频率幅度
跳跃频率幅度
跳跃频率幅度
Figure 6- 32 Principle of the skip frequency