CDE360 Vector Control AC Drive Chapter 6 Parameters Description
External brake
off current limit
The output current needs to be higher than EA.02 when the AC drive
begins to accelerate from the frequency of EA.01.
Base value is motor rated current.
External brake
off delay time
If the output current is higher than EA.02 and the output frequency
reaches EA.01,the Y terminal allocated with function No.44 "External
brake control" becomes OFF when the lasting time exceeds EA.03.
Acceleration
pause time for
external brake off
The AC drive stops accelerating for the time set by EA.04 when the Y
terminal allocated with function No.44"External brake control" becomes
OFF.Then it begins to accelerate.
Please set this parameter to suitable value according to the release time
of mechanical brake.
External brake on
frequency limit
When received a stop command,the AC drive decelerates to run at the
frequency of EA.05,and then
the Y terminal allocated with function No.44
"External brake control" becomes OFF
after the time set by EA.06.
External brake on
waiting time
See the parameter description of EA.05.
Stop delay time
after external
brake on
The AC drive goes to stop mode after the delay time set by EA.07 when
the Y terminal allocated with function No.44"External brake control"
becomes ON.This action is used to make sure that the mechanical brake
completely pulls.