Cellwatch Frontier System Installation & User Manual
Section III – Configuration Build and Hardware Integration Guide-113
4. Walk back through the Battery Design to make sure the configuration file was built correctly.
Choose Use Saved Settings and check the current layout. Make changes as needed.
CT Readings Incorrect
1. Check CT wiring at Frontier connection.
2. Check wiring at adapter box for the clamp. Verify the CT is plugged into the correct port number.
a. Port assignments can be checked by selecting Configure CTs.
3. Follow steps in Configure CTs option to Zero the readings before placing on the charger cables.
4. Verify CT configurations are correct according the type and capacity of the corresponding CT.
a. Type and capacity can be checked by selecting Configure CTs.
5. Check Physical CT Readings in Diagnostics.
a. Live output shows the constantly updating current readings for each physical CT.
TP Readings Incorrect
1. Check TP wiring at Frontier connection.
2. Ensure the TP Offset in Configure TPs is either not set or set correctly.
3. Check TP placement in string.
a. Avoid mounting the probe in areas where air changes or moves throughout the day. (Air
conditioning, heating, etc.)