Cellwatch Frontier System Installation & User Manual
Section III – Configuration Build and Hardware Integration Guide-108
15. Click Next.
16. Enter in the operator password of ‘deafcat’.
17. Click Save and wait for the “Settings Saved” confirmation.
18. Select Home from the Navigation Bar to see the new readings.
19. Assign alarms to the Frontier unit.
Inter-cell Straps
Example Configuration: 1 Battery, (1) 30 jar string measuring inter-cell straps, no inter-tier straps, 2
temperature probes, 2 current probes
1. Select Battery Design from the Settings menu.
2. Select Start new configuration.
3. Hardware
a. Wiring Pattern: Cells and Straps.
b. Temperature probes: TP1 and TP2.
c. Current transducers: CT1 and CT2.
d. Leave all digital bits checked unless they need to be disabled.
4. Click Next.
5. Name the Battery and String.
6. Assign TP1 and TP2 to String 1 by clicking the corresponding check boxes.
7. Assign CT1 and CT2 to String 1 by clicking the corresponding check boxes.
8. Assign DIBs as needed.
9. Enter “59” into the Channel count field (30 jars + 29 straps).
a. Left-click the 4
th
channel on the last DCM to null the last channel. This will not be
measured since that channel is a negative bus cable. See snapshot below for example
layout.
b. Make note of the number of DCMs needed for this configuration. Ensure the correct
amount of hardware is used. The channels for the inter-cell links will be numbered
independently of the cells. An example of the channel map is below.