Cellwatch Frontier System Installation & User Manual
Section I – Installation Guide-34
Ensure that the tab washers are fitted as close to the post of the cell or container being monitored.
Make sure that the tab washers are either against the battery post or against the inter-cell strap.
Other methods such as clip-on connectors can be used if approved by NDSL in advance. Use caution with
any connector as all exposed metal should be considered live. Clipped or C-Style connectors are
discouraged as they could become unsecured and create a short by touching grounded metal or the
battery.
Note: Do not place stainless steel washers, nuts, or any other hardware between the tab washers and
the battery post.