CG Drives & Automation,01-5326-01r5 Functional Description 135
DC Hold [33J]
This function makes it possible to apply a DC-voltage to the
motor at zero speed. This provides a (low) holding torque.
This function is only available in speed mode.
DC Hold [33J1]
Enabling of DC hold functionality.
Communication information
DC Holding Speed [33J2]
Select the speed at which DC hold is released / enabled.
DC hold is activated if both the speed and the speed
reference is below this value.
Communication information
DC Holding Current [33J3]
Select the applied DC hold current in percent of nominal
motor current.
Communication information
Start Vector [33K]
Select the voltage vector applied at start. The start vector is
normally in the direction of the U-phase. It is also possible
to sequentially select different start vectors each start. This
can be advantageous as it distributes the wear more evenly
between different IGBTs. In particular if DC-start is used.
The start vector may also be selected based on the encoder
position (when applicable).
Communication information
33J1 DC Hold
Default: Off
Off 0
On 1
Modbus Instance no/DeviceNet no: 43148
Profibus slot/index 169/52
EtherCAT and CANopen index (hex) 4c4c
Profinet IO index 19532
Fieldbus format UInt
Modbus format UInt
33J2 DC Hold Spd
Default: 10rpm
Range: 0 - 250 rpm
Modbus Instance no/DeviceNet no: 43149
Profibus slot/index 169/53
EtherCAT and CANopen index (hex) 4c4d
Profinet IO index 19533
Fieldbus format UInt, 1=1rpm
Modbus format UInt
33J3 DC Hold Cur
Default: 30 %
Range: 0 - 100 %
Modbus Instance no/DeviceNet no: 43150
Profibus slot/index 169/54
EtherCAT and CANopen index (hex) 4c4e
Profinet IO index 19534
Fieldbus format UInt, 1=1%
Modbus format UInt
33K Start Vector
Default: 0
Normal (U) 0 U-phase
Sequence 1 Sequentially selct different vectors
Encoder 2 Based on encoder position
Modbus Instance no/DeviceNet no: 43119
Profibus slot/index 169/23
EtherCAT and CANopen index (hex) 4c2f
Profinet IO index 19503
Fieldbus format UInt
Modbus format UInt