CG Drives & Automation, 01-5326-01r5 Installation 39
3.4.3 Cable connection data for mains, motor and PE cables according to
IEC ratings
NOTE: The dimensions of the power terminals used in the cabinet drive models 300 to 3K0 can differ depending on
customer specification.
Table 18 Cable connector range and tightening torque for Emotron VFX48 and VFX52, according to IEC ratings.
Model VFX
Frame
size
Cable cross section connector range
Cable
type
Mains and motor Brake PE
Cable area
mm
2
Tightening
torque
Nm
Cable area
mm
2
Tightening
torque
Nm
Cable area
mm
2
Tightening
torque
Nm
##-003-54
B 0.5 - 10 1.2-1.4 0.5 - 10 1.2-1.4 1.5 - 16 2.6
Copper
(Cu) /
Aluminum
(Al) 75°C
##-004-54
##-006-54
##-008-54
##-010-54
##-013-54
##-018-54
48-025-20
C2 4 - 25 2 4 - 25 2 4 - 25 * 4.3
48-030-20
48-036-20
48-045-20
48-058-20
##-026-54
C
2.5-16
stranded
2.5-25 solid
1.2-1.4
2.5-16
stranded
2.5-25 solid
1.2-1.4
6-16 stranded
6-25 solid
1.2-1.4
##-031-54
##-037-54
##-046-54
48-060-20 D2 0.75 -50 3.3 0.75 -50 3.3 10 - 70* 4.3
48-072-20
D2
0.75 -50 3.3 0.75 -50 3.3
10 - 70* 4.348-088-20
16 - 50 7.9 16 - 50 7.9
48-105-20
##-061-54
D
6-35
stranded
6-50 solid
2.8-3
6-35
stranded
6-50 solid
2.8-3
16-35
stranded
16-50 solid
2.8-3
##-074-54
48-142-20
E2
16- 150
31 (for
16-34 mm
2
)
42 (for
35-150 mm
2
)
16 - 120
31 (for
16-34 mm
2
)
42 (for
35-120
mm
2
)
16- 150
16 - 185 **
31 (for
16-34 mm
2
)
42 (for
35-150 mm
2
)
10 **
48-171-20
48-090-54
E
48-109-54
48-146-54
48-175-54

Table of Contents