Programmable DC Power Supply 62000P Series Operating & Programming Manual
Return Parameter: <NR1>
Query Example: CONF: OUTPut?
Return Example: 1 (ON) or 0 (OFF)
(5) CONFigure:FOLDback
Description: It sets the type of FOLDBACK PROTECT.
Syntax: CONFigure:FOLDback DISABLE
CONFigure:FOLDback CVTOCC
CONFigure:FOLDback CCTOCV
Parameter: 0/DISABLE, 1/CVTOCC, 2/CCTOCV
Example: CONFigure:FOLD DISABLE
CONFigure:FOLD CVTOCC
Query Syntax: CONFigure:FOLD?
Return Parameter: <NR1>
Query Example: CONF:FOLD? It returns the status set.
Return Example: 0 or 1 or 2
(6) CONFigure:FOLDT
Description: It sets the delay time of FOLDBACK PROTECT
Syntax: CONFigure:FOLDT <NRf1>
Parameter: 0.01~600.00 (Unit:Sec)
Example: CONF:FOLDT 10
Query Syntax: CONF:FOLDT?
Return Parameter: <NRf1>
Query Example: CONF:FOLDT?
Return Example: 1.000000e+01
(7) CONFigure:APGmode
Description: It sets the type APG mode.
Syntax: CONFigure:APGmode NONE
CONFigure:APGmode V
CONFigure:APGmode I
CONFigure:APGmode VI
Parameter: 0/NONE, 1/V, 2/I, 3/V&I
Example: CONF:APG V
CONF:APG VI
Query Syntax: CONFigure:APG?
Return Parameter: <NR1>
Query Example: CONF:APG? It returns the status set.
Return Example: 0 or 1 or 2 or 3
(8) CONFigure:APGV
Description: It sets the APG reference voltage.
Syntax: CONFigure:APGV FIVE
CONFigure:APGV TEN
Parameter: 0/FIVE, 1/TEN
Example: CONF:APGV FIVE
CONF:APGV TEN
Query Syntax: CONFigure:APGV?
5-10