InteliDrive DCU Industrial 3.4.0 Global Guide
163
Related FW 3.4.0 Related applications AS, SS
Comm object 149
Description
If the input is closed
Panel buttons Start and Stop are inactive
No setpoints can be adjusted from the controller front panel
Controller mode (e.g. OFF-RUN) cannot be changed
Fault reset (screen sensitive) and Horn reset buttons are still active
It is possible to list Setpoints, Values and History
Binary input functions are without change
Active Access lock is indicated by "L" in the upper right corner of controller screen.
Note: Access Lock does not protect Setpoints change, Mode change and START, STOP commands
from InteliMonitor and other external terminals. To avoid unqualified changes of the selected setpoints or
commands use password protection or activate the corresponding Access Lock for the used external
terminal.
AccessLock int
6 back to List of LBI
Related FW 3.4.0 Related applications AS, SS
Comm object 789
Description
If the input is closed, following commands received via RS232 interface (e.g. from InteliMonitor or from a
remote display) are inactive:
Remote engine start, stop commands
No setpoints can be adjusted
Controller mode (e.g. OFF-RUN) cannot be changed
Fault reset and horn reset commands
All other commands (e.g. change of a Remote Switch state)
It is possible to list Setpoints, Values and History
Binary input functions are without change
Engine can be started, stopped via Binary inputs (e.g. REMOTE START (PAGE 1)) or via front panel
buttons.
Note: When this Access Lock input is active, it is still possible to initiate programming from a remotely
connected DriveConfig.
AccessLockCOM1
6 back to List of LBI