InteliDrive DCU Industrial 3.4.0 Global Guide
50
0-10 V Y Y
0-100 mV Y Y
PT100 [°F] Y Y Y
PT1000 [°F] Y Y Y
NI100 [°F] Y Y Y
NI1000 [°F] Y Y Y
Thermocpl J[°F] Y Y Y Y
Thermocpl K[°F] Y Y Y Y
Thermocpl L[°F] Y Y Y Y
Tristate
Thermo(nc) J[°C] Y Y Y Y
Thermo(nc) K[°C] Y Y Y Y
Thermo(nc) L[°C] Y Y Y Y
Thermo(nc) J[°F] Y Y Y Y
Thermo(nc) K[°F] Y Y Y Y
Thermo(nc) L[°F] Y Y Y Y
0-5 V Y
0-10 kΩ Y
±65 V Y
±75 mV Y
Note:
* IGS-PTM has hardware range 0-20mA but offered sensor in DriveConfig is ±20mA
** IGS-PTM has hardware range 0-250Ω only - DriveConfig offers correct sensor for I/O configuration but for
User define input curve only sensor 0-2400Ω.
IGS-PTM 0-100 mV, 0-2400 Ω, ±20mA
IS-AIN8
0-100 mV; 0-2400 Ω; 0-2.4 V; 0-10V; ±20 mA; 0-20mA passive, 4-20mA
active; 4-20mA passive
I-AIN8
0-2.4V; 0-10V; 0-2400 Ω; ±20mA;0-20mA passive, 0-10 kΩ; 0-5V; 4-20mA
active; 4-20mA passive
I-AIN8TC +IS-AIN8TC none
I-AIO9 0-2k4Ω; ±65V; ±75V
User curves range
Note: Fahrenheit sensors are supported from IS-AIN8 of sw version 2.2 only.
Note: Controller user curves ("CU 'sensor range' ") are not possible to use for external extensions, it is
necessary to configure standard user curve (= without "CU" on the beginning of the name of the user curve
range).
4.3.6 Binary inputs/outputs on ID-DCU Industrial
Use wiring cables min. of 1.0 mm2 to ensure proper function.