The InteliDrive DCU Industrial controller should be grounded properly in order to protect against atmospheric
discharges!
Install separate conductors for signal and power inputs. Allow for conductor voltage drop when determining
conductor size. All power supplies must have common ground.
When there is a potential risk of the controller being subjected to conditions outside its capabilities - an outside
protection device should be used.
4.3.2 Analog as Binary input
To use Analog input as binary configure following characteristics:
Primary Converted
0 0
1000 1
4.3.3 Analog as three state (tristate) binary input
Open, close and failure (broken wire, short wire) states are detected. Threshold level is 750 Ω, failure is
detected when circuit resistance is <10 Ω or > 2400 Ω
4.3.4 Analog Sensor availabilty with controller
Table of supported sensors with controller.
InteliDrive-AI1-4 InteliDrive AI5-8
PT100 [°C] Y
PT1000 [°C] Y Y
NI100 [°C] Y
NI1000 [°C] Y Y
PT100 [°F] Y
PT1000 [°F] Y Y
NI100 [°F] Y
NI1000 [°F] Y Y