InteliDrive DCU Industrial 3.4.0 Global Guide
312
8.2.5 Inteli AIO9/1 (I-AIO9/1)
Description
Inteli AIO9/1 module is extension module equipped with analog inputs and outputs designed for DC
measurement.
The module can be used for ID-DCU, InteliMains-NT, InteliGen-NT and InteliSys-NT controllers.
This module is compatible with MTU ECU-7 at communication speed 125 kbps when uploaded with firmware
1.2.0 and higher.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication speed
detection is done by reset of the module.
Available inputs/outputs
Analog inputs
4 channels AIN1 AIN4 can be configured as:
Sensor ±65V (it is determinated for measurement of battery voltage)
4 channels AIN5 AIN8 can be configured as:
Thermocouples type J,K or L (in °C or °F)
Sensor ±75mV DC (for connecting current shunts)
1 channel AIN9 can be configured as:
RTD (Pt1000, Ni1000)
Common resistance 0-2400Ω

Table of Contents