InteliDrive DCU Industrial 3.4.0 Global Guide
311
Relays inputs (galvanic separated)
Voltage level is defined between binary input and binary input COM terminal
Number of inputs 8 + 8
Input resistance 3000 Ω
Input voltage range 0-36 VDC
Input voltage level for open contact 8 to Power supply VDC
Input voltage level for close contact 0 to 2 VDC
Frequency inputs* (for IS-CU only)
RPM1
Type of sensor Magnetic pick-up
Minimum input voltage 2 Vpk-pk (from 4 Hz to 4 kHz)
Maximum input voltage 50 Veff
Maximum measured frequency 8 kHz (min. input voltage 6Vpk-pk), frequency mode
RPM2
Type of sensor Contact or Active sensor
Minimal pulse width 10 ms, integration mode
Maximum measured frequency 60 Hz, integration mode
Relays outputs (galvanic separated) only HW 3.0 (non galvanic separated) HW 2.1
Number of output 8
Maximum current 0.5A DC
Maximum switching voltage 36 VDC
Power supply 8 to 36 V DC
Protection front panel IP20
Current consumption 250 mA** at 24 V
Humidity 95% without condensation
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 2 W
Standard conformity
Number of output 8
Low Voltage Directive EN 61010-1:95 +A1:97
Electromagnetic Compatibility
EN 50081-1:94, EN 50081-2:96
EN 50082-1:99, EN 50082-2:97
*RPM1, RPM2 are available in IS-CU only **During powering up current can be up to 1.5A