InteliDrive DCU Industrial 3.4.0 Global Guide
292
Impulse
Measurement of pulses by norm DIN 43864 and norm IEC 62053-31 equipment class A.
For flow meter pulses: UH=30V, Imax=30mA, Ton min =10ms,Toff min = 10ms , OC
Galvanic separation
CAN bus is galvanic separated from the measurement and power supply.
All analog inputs are galvanic separated from power supply.
Analog inputs are not galvanic separated between channels
Power supply 8 to 36 V DC
Protection IP20
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 3 W
*RPM input required level of signal for correct sensing
Minimum input voltage 2 Vpk-pk (from 4 Hz to 4 kHz)
Minimum input voltage 6 Vpk-pk (from 4 kHz to 10 kHz)
*Voltage measurement circuit was designed for lambda probe, for measurement thermocouples please use
Inteli AIN8TC.
The product is fully supported in fw IGS-NT 3.0 or higher and in IGS-NT-branches based on this fw.
6 back to Extensional modules
8.2.2 Inteli AIN8TC
Image 8.4 Dimensions of Inteli AIN8TC
Inteli AIN8TC unit can be mounted on DIN rail (35 mm). All dimensions are in mm.