InteliDrive DCU Industrial 3.4.0 Global Guide
35
The only one low temperature sensitive part is the controller display.
ID-DCU -LT version contains a preheating foil on the display activated below +5°C (measured on the PCB).
Heating is switched off when controller power supply is below 10VDC (together with display backlight).
4.1.8 ID-SCM Speed control module
ID-SCM module is interface module for InteliDrive controller application. Module is mounted directly to ID-DCU
Industrial controller case. Module power supply: 8 to 36VDC.
Inputs
RPM1, RPM2: Two inputs for frequency (e.g. flow) measuring. Expected sensor is magnetic pickup with
maximal frequency range up to 8 kHz. The output values SCM Freq1, SCM Freq2 calculation use setpoints
SCM unit: FreqRate1 and FreqRate2 - see below.
Closed jumper divides input frequency by 16 - recommended for higher frequency (>1000Hz) measuring.
Jumper position does not influence output value range.
Jumper RPM input nominal frequency range
Closed > 1000 Hz
Closed or Opened 500 - 1000 Hz
Opened 500 Hz
IMP1, IMP2: Two impulse inputs for integral (e.g. consumption) measuring. It is expected NPN open collector
(active) impulse sensor with maximal frequency range up to 60 Hz. Minimal pulse duration is 1ms. The output
values SCM Imp1, SCM Imp2 calculation use setpoints SCM unit: TransferRate1 and TransferRate2 - see
below.
ID-SCM inputs wiring example
Magnetic pickup wiring to
RPM1 and RPM2 inputs.