7 Technical data
7.1 ID-DCU Industrial
Nominal power supply 24 VDC
Power supply range 8 36 VDC
Current consumption (depends on supply voltage)
0.34 A at 8 VDC
0.12 A at 24 VDC
0.09 A at 36 VDC
Galvanically isolated from controller body YES
Battery voltage measurement tolerance 2 % at 24 V
RTC battery life-cycle 10 year
Power supply
Note: RTC battery flat causes wrong Date&Time information only.
Operating temperature ID-DCU Industrial -20 to +70 °C
Storage temperature -30 to +80 °C
Humidity 95 % non-condensing (EN 60068-2-30)
Flash memory data retention time 10 years
Protection front panel IP65
Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
Electromagnetic Compatibility
EN 61000-6-2, October 2001
EN 61000-6-4, October 2001
IEC 60533, Ed. 2; 1999-11
Vibration
5 25 Hz, ±1.6mm
25 100 Hz, a = 4 g
Shocks a = 200 m/s2
Heat radiation 9 W
Operating conditions
Dimensions
(183×123×47 mm)
See chapter terminals and dimensions
Weight 800 g
Dimensions and weight