InteliDrive DCU Industrial 3.4.0 Global Guide
52
4.3.8 Connection of ID-DCU Industrial analog inputs
Standard connection of resistive sensors to ID-
DCU Industrial analog inputs AI1 to AI8. The COM
terminal must be always connected to the negative
power terminal.
Different sensors connection to ID-DCU Industrial.
AI configuration jumpers must be in corresponding
position and corresponding DriveConfig
configuration according to used sensor.
Analog input common terminal COM has to be
connected to ID minus Power supply terminal.
Mixed connection of ID-DCU Industrial analog
inputs:
AI2, AI7 - current sensor
AI1, AI5 - resistive sensor
AI3, AI8 - voltage input
AI6- thermocouple (voltage)
AI4 - Not used
Mixed connection of InteliDrive analog inputs:
AI1, AI2, AI5, AI6 - resistive sensor
AI3, AI7 - binary input
AI4, AI8 - three state input
Analog input common terminal COM has to be
connected to ID minus Power supply terminal.
To ensure a proper function use shielded cables, especially for length over >3 m.
4.3.9 ID-DCU Industrial Analog inputs hardware configuration
Configure Analog inputs AI1-AI8 connection by jumpers on PCB (remove cover).

Table of Contents