Measuring voltage
Ranges: ±1 V, 0 – 2,5 V, 0 – 5 V, 0 – 10 V
Impulse input
1 channel
Can be configured as
Impulse
Impulse/time
RPM
All inputs can be configured to any logical function or protection.
It is possible to connect up to 10 modules to the InteliGen-NT, InteliSys-NT or InteliMains-NT controllers or up
to 4 modules to the ID-DCU.
Inteli AIN8 module is connected to controller CAN1 bus.
Technical data
Dimension (W × H × D) 110 × 110 × 46 mm (4,3” × 4,3” × 1,8”)
Weight 221.5 grams
Interface to controller CAN1
Analog inputs (not electric separated) 8 channels
*Voltage
Range 0-10 V
Accuracy ± 0,25 % of actual value + ± 25 mV
Current
Range ±20 mA
Accuracy ± 0.25 % of actual value + ± 50 µA
Resistance
Range 0- 10 kΩ
Accuracy ± 0.5 % of actual value + ± 2 Ω
Resistance Pt100, Pt1000, Ni100, Ni1000 ± 2,5 °C
Impulse input
*RPM
Level of signal 2 Vpk-pk ÷ 70 Vpk-pk
Frequency range 4 Hz ÷ 10 kHz