InteliDrive DCU Industrial 3.4.0 Global Guide
310
Power supply fusing
A (2) respectively (1) amp fuse should be connected in-line with the power to the controller and modules, these
items should never bee connected directly to the starting battery.
Take care for proper controller, extension units and relays power supply fusing. Fuse value and type depends on
number of connected devices and wire length.
Controller or unit Fuse
Controller T1A or T2A
IS-AIN8 T2A
IS-BIN16/8 T1A
Table 8.3 Recommended fuse (not fast) types
For more extension units use separate fusing according to the table above.
Controller power supply should never be connected to starter terminals.
Technical data
Dimension (W × H × D) 146 × 160 × 46 mm (5.79’ × 6.6’ × 1.83’)
Interface to controller CAN1