InteliDrive DCU Industrial 3.4.0 Global Guide
323
Sensor IS-AIN8
None
I-CB analog Value is received from I-CB
Pt100/°C
Use button to create new sensor characteristic.
Pt1000/°C
Ni100/°C
Ni1000/°C
Thermocouple J/°C
Thermocouple K/°C
Thermocouple L/°C Adjust Range = maximal measured value
4 to 20 mA passive Adjust Range
4 to 20 mA active Adjust Range
0 to 20 mA passive Adjust Range
0 ± 20 mA active Adjust Range
0-250 ohm Adjust Range
0-2400 ohm Adjust Range
0 2.4 V
±1 V
0 - 10 V
0 - 100mV
Pt100/°F
Pt1000/°F
Ni100/°F
Ni1000/°F
Thermocouple J/°F
Thermocouple K/°F
Thermocouple L/°F
Cold Junction Compensation (CJC)
Cold junction compensation is also called reference junction compensation. When measuring temperature using
thermocouples, the reference terminal may not be held at 0°C, but at the surrounding temperature of T1°C
instead. Without any compensation, the thermocouple output will be changed (reduced) by T1°C. This is
compensated by adding potential difference to the IS-AIN8 corresponding to T1°C.