InteliDrive DCU Industrial 3.4.0 Global Guide
329
AIN1 – AIN8 8 analog inputs
CAN CAN1 line
POWER Power supply
POWER State indication
Rx, Tx Data transmitted and received on CAN1 line
LDD CAN1 address
Address and jumper settings
CAN1 address is set by following procedure:
1. Press Address button during IS-AIN8TC power supply on to switch to addressing mode.
2. Then repeatedly press or keep pressed address button to adjust required address according to controller
configuration.
3. After setting requested address, release the buttons and wait until the digits blink – it indicates writing of the
change address to EEPROM memory.
CAN11 Address
1. IS-AIN8TC 1
2. IS-AIN8TC 2
3. IS-AIN8TC 3
4. IS-AIN8TC 4
5. IS-AIN8TC 5
6. IS-AIN8TC 6
7. IS-AIN8TC 7
8. IS-AIN8TC 8
9. IS-AIN8TC 9
10. IS-AIN8TC 0
Table 8.7 Table of recommended CAN1 address setting
SW version check
Shortly press address button. Following sequence appears on the display: number “1”, one second pause,
number “4”, two second pause, number “1”, one second pause, number “4”, two second pause and finally IS-
AIN8TC actual address.
Error message (e.g. SD BOUT2) appears on Controller screen when Binary input or output Address x is
configured but corresponding unit is not recognized (no message is received from CAN bus). Check IS
configuration and corresponding external IS-AIN8TC, IS-BIN8/16 unit address setting.
LED indication
Power LED Address LDD
Lighting Blink Lighting Blink
Power supply and CAN
address are with no
problems
CAN1 address is adjusted
different in IS-AIN8TC
and in controller
Displaying current CAN1
address
Displaying current SW
version