InteliDrive DCU Industrial 3.4.0 Global Guide
33
Note: Put jumper to connect the internal 120Ω terminating resistor for CAN2 interface. ID-COM module is not
required when inter-controller CAN2 line is not used. In this case connect Extension modules CAN1 directly to
Extension modules port ID-COM on ID-DCU Industrial (9-pin connector: 5=H, 9=L).