Technical data
Dimension (W × H × D) 95 × 96 × 43 mm (3.7’ × 3.8’ × 1.7’)
Interface to controller CAN1
Binary inputs
Input resistance 4700 Ω
Input range 0 to 36V DC
Type Pull Up
Switching voltage level for open contact indication 0 to 2 V
Max voltage level for open contact indication 8 to 36 V
Binary output (Open collector output)
Type Low side switch (LSS)
Max current 500 mA
Max switching voltage 36V DC
Analog inputs (Not electric separated)
Resolution 10 bits
Sensor resistance range 0 to 250 Ω
Maximal voltage range 0 to 100 mV
Maximal current range 0 to 20 mA
Resistance measurement tolerance 1 % ± 2 Ω out of measured value
Voltage measurement tolerance 1.5 % ± 1 mV out of measured value
Current measurement tolerance 2.5 % ± 0.5 Ω out of measured value
Input impedance for measuring current 3.9 Ω
Input impedance for measuring voltage 100 kΩ
Analog output (not electric separated)
Output current 0 to 20 mA ± 0.33 mA
Resolution 10 bit
Power supply 8 to 36 V DC
Protection IP20
Current consumption 100 mA at 24V ÷ 500 mA
Storage temperature - 40 °C to + 8 0°C
Operating temperature - 30 °C to + 80 °C
Heat radiation 8 W
6 back to Extensional modules