InteliDrive DCU Industrial 3.4.0 Global Guide
66
3. Add another protections in EXPERT window. There can be set the same delay for all four limits.
Set up protection activation
Setting the "Active when" parameter has several options with a specific evaluation.
Image 5.1 Select when the protection will be activated - DriveConfig
Under limit
Protection is announced when it gets below the limit Level 1 (and Level 2) Limit Setpoint: Value. The delay of
Delay Setpoint: Value can be applied to the protection. Alarm notification in the alarm list and in history
Sensor defect when receiving invalid or no value, announces the Fls Analog input name (where Analog input
name = will be the specific electronic (ECU, I-CB, shared) value on which the protection is configured)
Over limit
Protection is announced when it gets over the limit Level 1 (and Level 2) Limit Setpoint:Value. The delay of
Delay Setpoint:Value can be applied to the protection. Alarm notification in the alarm list and in history
Sensor defect when receiving invalid or no value, announces the Fls Analog input name