CTH200 Series PLC User Manual
79
Table 4-5-13 SM231-7ND module specifications
Order No.
CTH2 231-7ND32
Features
Dimension (W×D)
71.3 × 96 × 62mm
LED indicator
24VDC indicator: ON=No fault, OFF=No 24VDC power
SF Indicator: ON=Module fault, Flash=Out range or disconnect,
OFF=No fault
Power supply
+5VDC current
87mA
L+
60mA
L+ coil voltage range
20.4~28.8VDC
Power
1.7W
Input
Thermistor input range
Thermistor Type:
Pt-100(3850ppm, 3920ppm, 3850.55ppm, 3916ppm, 3902ppm)
NTC(R25=10kΩ/B=3950, R25=10kΩ/B=3435)
Temperature Range
Pt-100: -50~850
NTC(R25=10K, B=3950): -40~120
NTC(R25=10K, B=3435): -40~150
Voltage input
0V~5V, 0V~10V, ±5V, ±10V
Current input
0~20mA
Input counts
2PT100/2NTC and 2AI
Isolation
Field to Logic
500VAC
Field to 24VDC
500VAC
24V to Logic
500VAC
Common mode rejection
>120dB@120VAC
Sampling
Temperature resolution
0.1/0.1
Voltage resolution
15bits sign bit
Transfer principle
Σ-Δ
Module update time: All
channels
425ms
Wire length to sensor
Max. 100m
Conductor loop resistance
Max. 20Ω
Suppression of
interference
85dB@50Hz/60Hz/400Hz
Data word format
Temperature (NTC: R25=10kΩ, B=3950K): -400~1200(only for
channel 1/2)
Temperature (NTC: R25=10kΩ, B=3435K): -400~1500(only for
channel 1/2)
Temperature (PT100): -500~2000(only for channel 1/2)
Voltage/Current: Unipolar 0~32000, Bipolar -32000~+32000(only
for channel 3/4)