AGC Designer’s Reference Handbook
DEIF A/S Page 113 of 168
Status text Condition Comment
Stopping DG(s) ###s When the stop gen-set
setpoint is exceeded, this info.
is shown with the countdown
of the timer.
Start prepare This info. is shown during the
time the start prepare relay is
activated.
Start ON This info. is shown during the
time the start relay is activated
during the start sequence.
Start OFF This info. is shown during the
time the start prepare relay is
deactivated.
Mains failure This text appears as soon as
a frequency or voltage
measurement is outside the
limits.
Mains failure in ###s This text appears as soon as
a frequency or voltage
measurement is outside the
limits. The timer shown is the
mains failure delay.
Mains U OK del ####s When the mains voltage is OK
after a mains failure, this info.
is shown with the countdown
of the timer.
Mains f OK del ####s When the mains frequency is
OK after a mains failure, this
info. is shown with the
countdown of the timer.
Volt./freq. OK in ###s As soon as the voltage and
frequency on the gen-set are
OK, this text is shown until it is
allowed to operate the
generator breaker.
Cooling down ###s When the cooling down period
is started, this info. is shown
with the countdown of the
timer.
Gen-set stopping This info. is shown when cool
down has finished.
Ext. stop t. ###s
Blackout enable This info. is shown, if a CAN
failure is present in a power
management application.
Option G5 must be available.
Programming language This info. is shown, if the
language file is downloaded
from the PC utility software.