AGC Designer’s Reference Handbook
DEIF A/S Page 154 of 168
2640 Relay control
No. Setting Min. setting Max. setting Factory
setting
2641 Relay control GOV ON time 10 ms 3000 ms 500 ms
2642 Relay control GOV per. time 50 ms 15000 ms 2500 ms
2690 Delay regulation
No. Setting Min. setting Max. setting Factory
setting
2691 Delay regulation Timer 0 s 9900 s 0 s
2692 Delay regulation Output A R0 (none) R0 (none)
2693 Delay regulation Output B R0 (none)
Option
dependent
R0 (none)
2694 Delay regulation Enable OFF ON OFF
2700 Short time paralleling
No. Setting Min. setting Max. setting Factory
setting
2701 Short paralleling Enable OFF ON OFF
2702 Short paralleling Timer 0.10 s 99.90 s 0.30 s
Input/output
This menu consists of parameters for configuration of the inputs and outputs.
Binary input setup
3260 Dig. input no. 110 (option M2)
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
3261 Dig. input no. 110 Timer 0.0 s 100.0 s - 10.0 s
3262 Dig. input no. 110 Relay output A R0 (none) - R0 (none)
3263 Dig. input no. 110 Relay output B R0 (none)
Option
dependent
- R0 (none)
3264 Dig. input no. 110 Enable OFF ON RUN OFF
3265 Dig. input no. 110 Fail class Alarm (1) Trip MB (6) - Warning (2)
3266 Dig. input no. 110 Type N/O N/C - N/O
3270 Dig. input no. 111 (option M2)
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
3271 Dig. input no. 111 Timer 0.0 s 100.0 s - 10.0 s
3272 Dig. input no. 111 Relay output A R0 (none) - R0 (none)
3273 Dig. input no. 111 Relay output B R0 (none)
Option
dependent
- R0 (none)
3274 Dig. input no. 111 Enable OFF ON RUN OFF
3275 Dig. input no. 111 Fail class Alarm (1) Trip MB (6) - Warning (2)
3276 Dig. input no. 111 Type N/O N/C - N/O