AGC Designer’s Reference Handbook
DEIF A/S Page 166 of 168
6170 Starter
No. Setting Min. setting Max. setting Factory
setting
6171 Starter Start prepare 0.0 s 600.0 s 5.0 s
6172 Starter Start ON time 1.0 s 30.0 s 5.0 s
6173 Starter Start OFF time 1.0 s 99.0 s 5.0 s
6180 Start attempts
No. Setting Min. setting Max. setting Factory
setting
6181 Start attempts Attempts 1 10 3
6182 Start attempts Relay output A R0 (none) R0 (none)
6183 Start attempts Relay output B R0 (none)
Option
dependent
R0 (none)
6184 Start attempts Fire start attempt 1 10 7
6185 Start attempts FP cool down 0.0 s 990.0 s 30.0 s
6190 f/U OK
No. Setting Min. setting Max. setting Factory
setting
6191 f/U OK Timer 1.0 s 99.0 s 5.0 s
6200 f/U failure
No. Setting Min. setting Max. setting Factory
setting
6201 f/U failure Timer 1.0 s 99.0 s 30.0 s
6202 f/U failure Relay output A R0 (none) R0 (none)
6203 f/U failure Relay output B R0 (none)
Option
dependent
R0 (none)
6210 Stop
No. Setting Min. setting Max. setting Factory
setting
6211 Stop Cool down time 0.0 s 990.0 s 240.0 s
6212 Stop Extended STOP 1.0 s 99.0 s 5.0 s
6213 Stop Coil type STOP RUN RUN
6220 Stop failure
No. Setting Min. setting Max. setting Factory
setting
6221 Stop failure Timer 10.0 s 120.0 s 30.0 s
6222 Stop failure Relay output A R0 (none) R0 (none)
6223 Stop failure Relay output B R0 (none)
Option
dependent
R0 (none)
6250 GB control
No. Setting Min. setting Max. setting Factory
setting
6251 GB control Timer t
GBC
0.0 s 30.0 s 2.0 s
6252 GB control GB load time 0.0 s 30.0 s 0.0 s
The number of start attempts adjusted in menu 6184 Fire start attempt, is used
when the digital input ‘fire pump’ is used instead of the setting 6181.