AGC Designer’s Reference Handbook
DEIF A/S Page 62 of 168
Setup example
The following example illustrates how a specific setting is changed in the setup menu. In this
case
Reverse power is the selected parameter.
G 439 440 440V
1010 Reverse Power
Setpoint -5.0 %
LIM
DEL OA OB ENA FC
first entry
G 439 440 440V
1020 Over current 1
Setpoint 115.0 %
LIM
DEL OA OB ENA FC
G 439 440 440V
Enter passw. 1999
ENTER
G 439 440 440V
1011 Reverse power
-50.0 -5.0
0.0%
RESET
SAVE
Yes
No
BACK SEL
INCREASE NO
DECREASE NO
Increase setting
Decrease setting
moves the cursor
G 439 440 440V
PROTECTION SETUP
SET POINT 1 SETUP
PROT1
PROT2
SELBACK
Mode overview
The unit has four different running modes and one block mode. For detailed information see
page 11.
Auto
In auto mode the unit will operate automatically, and the operator cannot initiate any sequences
manually.
Semi-auto
In semi-auto mode the operator has to initiate all sequences. This can be done via the push-
button functions, Modbus commands or digital inputs. When started in semi-automatic mode,
the gen-set will run at nominal values.
Test