AGC Designer’s Reference Handbook
DEIF A/S Page 81 of 168
Time dependent start/stop
The purpose of the time dependent start/stop function is to be able to start and stop the gen-set
automatically at specific times each weekday or certain weekdays. If auto mode is activated, this
function is available in island operation, load take over, mains power export and fixed power
operation. Up to 8 commands can be used for either start or stop. The settings are set up
through the PC utility software. Each command can be set for the following time periods:
Individual days (MO, TU, WE, TH, FR, SA, SU)
MO, TU, WE, TH
MO, TU, WE, TH, FR
MO, TU, WE, TH, FR, SA, SU
SA, SU
The digital input ‘auto start/stop’ cannot be used, when this function is enabled.
Mains OK
MB i nput
configured
MB and GB
operations
MB control
input
Yes
ON
No
Mains OK
delay
No
expired
Yes
No Yes
Sequence