AGC Designer’s Reference Handbook
DEIF A/S Page 21 of 168
The settings for the test function are set up in menu 6540 Test running
.
Setpoint: Load setpoint when paralleling to mains.
Timer: Engine run time during the test period
Return: When the test is completed, the unit will return to the selected mode
(semi-auto or auto).
General manual mode description
When manual mode is selected, the gen-set can be controlled with digital inputs. The following
commands are possible:
Command Comment
Start Gen-set starts.
Stop Gen-set opens GB and stops
without cooling-down.
Manual increase speed Unit gives increase signal to
speed governor.
Manual decrease speed Unit gives decrease signal to
speed governor.
Manual increase voltage Unit gives increase signal to
the AVR. (Option D1).
Manual decrease voltage Unit gives decrease signal to
the AVR. (Option D1).
General block mode description
When the block mode is selected, the unit is locked for certain actions. This means that it cannot
start the gen-set or perform any breaker operations.
To change the running mode from the display, the user will be asked for a password, before the
change can be made. It is not possible to select ‘block mode’, when running feedback is
present.
Short time parallel is ignored in test mode.
Test mode cannot be used, if the gen-set is in island operation (gen-set mode
selected to island mode).
It is not possible to open and close the generator breaker or the mains breaker
in manual mode.
It is necessary to configure the digital inputs through the PC utility software to
use the manual commands. The number of configurable digital inputs is option
dependent.
MAN mode cannot be selected, when AUTO mode is selected. To go from AUTO
to MAN it is necessary to go to SEMI-AUTO to make MAN available.