SGB close blocked
The Block SGB close function is active. An open breaker
cannot be closed.
SGB close cancelled The SGB close was cancelled by a SGB open command.
SGB close not possible in
SWBD
While the controller is under switchboard control, operator
actions cannot be performed from the controller
interfaces.
SGB close unblocked The Block SGB close function is not active.
SGB open cancelled The SGB open was cancelled by a SGB close command.
SGB open not possible in
SWBD
While the controller is under switchboard controller,
operator actions cannot be performed from the controller
interfaces.
Start enable not activated
The genset cannot start, because Start enable is not
activated.
Static synchronisation
activated
The digital input is activated. The controller will use static
synchronisation.
Static synchronisation
deactivated
The digital input is deactivated. The controller will use the
synchronisation type configured in the parameter.
Synchronisation cancelled
The controller has cancelled the synchronisation (for
example, if there is a blackout during synchronisation).
OPERATOR'S MANUAL 4189341099G UK Page 14 of 130