Chapter 4 Parameters|
4-20 Revision August 2008, 03VE, SW V2.04
Pr. Explanation Settings
Factory
Setting
VF
VFPG
SVC
FOCPG
TQRPG
08-65
Error Treatment of Tension
PID Feedback
0: Warn and keep operation
1: Warn and coast to stop
2: Warn and ramp to stop
0
08-66
Upper Limit of Tension PID
Feedback
0.0~100.0% 100.0
08-67
Lower Limit of Tension PID
Feedback
0.0~100.0% 0.0
08-68
Reserved
08-69
DFM Selection 0: Output frequency
1: Frequency command
0
08-70
Low-pass Filter Time of
Line Speed
0.00~100.00 sec 0.00
08-71
|
08-75
Reserved
08-76
Source of Tension Setting
0: Communication RS-485 (Pr.08-78)
1: Analog input (Pr. 03-00~03-02 is set to 15 tension
setting) (Pr.08-78)
0
08-77
Max. Tension 0~30000 N 0
08-78
Tension Setting 0~30000 N 0
08-79
Source of Zero-speed
Tension Setting
0: Disable
1: Communication RS-485 (Pr.08-80)
2: Analog input (Pr. 03-00~03-02 is set to 16 zero-
speed tension) (Pr.08-80)
0
08-80
Setting of Zero-speed
Tension
0~30000 N 0
08-81
Source of Tension Taper 0: Communication RS-485 (Pr.08-82)
1: Analog input (Pr. 03-00~03-02 is set to 17 tension
taper)(Pr.08-82)
0
08-82
Tension Taper 0~100% 0
08-83
Friction Compensation 0.0~100.0% 0.0
08-84
Compensation Coefficient
of Material Inertial
0~30000 0
08-85
Torque Feedforward Gain 0.0~100.0% 50.0
08-86
Low Pass Filter Time of
Torque Feedforward
0.00~100.00 5.00
08-87
|
08-99
Reserved