Group 70 — Protective Functions
MVX9000 User Manual 5-55
Descriptions of 
Parameter Settings
Figure 5-48: Over-Current Stall Prevention
70.03
Over-Current Stall
Prevention during
Operation
Range: Default: 150%
00: disable
20 to 200%: enable
Unit: 1%
During steady-state operation with the motor load rapidly 
increasing, the AC drive output current may exceed the limit 
specified in 70.03. When this occurs, the output frequency will 
decrease to prevent an Over Current Fault. The drive will 
accelerate back to the command frequency only when the 
output current drops below the level specified by 70.03.
70.04
Over-Torque
Detection Mode(OL2)
Range: Default: 00
00 Over-Torque detection disabled
01 Over-Torque detection enabled during constant speed 
operation, and operation halted after Over-Torque 
Detection
02 Over-Torque detection enabled during constant speed 
operation, and operation continues after Over-Torque 
Detection
03 Over-Torque detection enabled during operation, and 
operation halted after Over-Torque Detection
04 Over-Torque detection enabled during acceleration, and 
operation continues after Over-Torque Detection