Group 90 — Communications
MVX9000 User Manual 5-65
Descriptions of
Parameter Settings
Table 5-3: Communication Mapping Table
90.06 to 90.23
Communication Only
Parameters
These parameters are used when controlling and monitoring
the MVX with a PC. See Table 5-3.
Modbus Groups Description Range
0705H 90.06 Communication frequency
reference
0.0 to 400.0 Hz (Default: 0.0)
0706H 90.07 Communication command Bit 0-1: 00 no function
01 Stop
10 Run
11 JOG + Run
Bit 2-3: Reserved
Bit 4-5: 00 no function
01 Forward
10 Reverse
11 Change direction
Bit 6-15: Reserved
0707H 90.08 Communication for EF/
RESET
Bit 0: 1 EF On
Bit 1: 1 Reset
Bit 2-15: Reserved
0708H 90.09 Status monitor for error
code
00: No Fault occurred
01: Over-current (oc)
02: Over-voltage (ov)
03: Overheat (oH)
04: Overload (oL)
05: Overload 1 (oL1)
06: Overload 2 (oL2)
07: External Fault (EF)
08: CPU Failure 1 (CF1)
09: CPU Failure 2 (CF2)
10: CPU Failure 3 (CF3)
11: Hardware Protection Failure (hpF)
12: Over-current During Accel (OCA)
13: Over-current During Decel (OCd)
14: Over-current During Steady State
(OCn)
15: Ground Fault or Fuse Failure
(GFF)
16: Reserved
17: 3-Phase Input Power Loss
18: External Pause Function (bb)
19: Auto Adjust Accel/Decel Failure
(cFA)
20: Software Protection Code (codE)