Group 60 — Motor Control
5-50 MVX9000 User Manual
Descriptions of
Parameter Settings
Group 60 — Motor Control
60.01
Motor Rated Current Default: xx.x A
Enter the motor’s nameplate rated amps.
The value must be between 30 to 120% of the drive’s rated
output current. This parameter sets the drive’s output current
limit.
This parameter may be set during operation.
60.02
Motor No-Load
Current
Default: xx.x A
Enter the motor’s no-load current in amps. If the motor no-
load amps are not known, leave this parameter at factory
default.
The value must be between 0 to 99% of the drive’s rated
output current and also less than parameter 60.01.
60.02 has a great effect on how accurate the slip
compensation function works. An incorrect setting will cause
poor slip compensation.
This parameter may be set during operation.
60.03
Motor Auto Tuning Range: Default: 00
00 Disabled
01 DC test only
02 DC test and no load test
To conduct the auto tuning feature, select 01 or 02 and then
press “START”. If the motor is loaded, it is recommended to
select 01.
60.04
Motor’s Stator
Resistance
Range: 00 to 65535 m Ohms Default: 00
Units: milli-ohms
This parameter determines the motor’s line-to-line resistance.
The value may be entered manually or via the Auto Tune
feature 60.03. This value should be entered when using
Sensorless Vector control.