Group 60 — Motor Control
5-50 MVX9000 User Manual
Descriptions of 
Parameter Settings
Group 60 — Motor Control
60.01
Motor Rated Current Default: xx.x A
Enter the motor’s nameplate rated amps.
The value must be between 30 to 120% of the drive’s rated 
output current. This parameter sets the drive’s output current 
limit.
This parameter may be set during operation.
60.02
Motor No-Load
Current
Default: xx.x A
Enter the motor’s no-load current in amps. If the motor no-
load amps are not known, leave this parameter at factory 
default.
The value must be between 0 to 99% of the drive’s rated 
output current and also less than parameter 60.01.
60.02 has a great effect on how accurate the slip 
compensation function works. An incorrect setting will cause 
poor slip compensation.
This parameter may be set during operation.
60.03
Motor Auto Tuning Range: Default: 00
00 Disabled
01 DC test only
02 DC test and no load test
To conduct the auto tuning feature, select 01 or 02 and then 
press “START”. If the motor is loaded, it is recommended to 
select 01.
60.04
Motor’s Stator
Resistance
Range: 00 to 65535 m Ohms  Default: 00
Units: milli-ohms
This parameter determines the motor’s line-to-line resistance. 
The value may be entered manually or via the Auto Tune 
feature 60.03. This value should be entered when using 
Sensorless Vector control.