EasyManua.ls Logo

Eaton MVX9000 - Figure 5-14: Digital Input Terminal Settings 05, 06, 07

Eaton MVX9000
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Group 30 — Inputs
MVX9000 User Manual 5-17
Descriptions of
Parameter Settings
Settings 05, 06, 07
These three inputs select the preset speeds defined by P30.18 to P30.24.
Figure 5-14: Digital Input Terminal Settings 05, 06, 07
Switch 1 Switch 2 Switch 3
P30.18 ON OFF OFF
P30.19 OFF ON OFF
P30.20 ON ON OFF
P30.21 OFF OFF ON
P30.22 ON OFF ON
P30.23 OFF ON ON
P30.24 ON ON ON
ON
Master Freq.
Switch 1
Switch 2
Switch 3
Operation
Command
ON ON ON
ON ON ON ON
ON ON ON ON
ON OFF
Time
Frequency
30.18
Step 1
30.19
Step 2
30.20
Step 3
30.21
Step 4
30.22
Step 5
30.23
Step 6
30.24
Step 7
07:Multi Speed 3
06:Multi Speed 2
05:Multi Speed 1
RO3 RO2 RO1
DI1 DI2
DI3
DI4
DI5
DI6
COM
AO+
AI1
+10V
AI2
DO1
DOC
COM

Table of Contents