Group 50 — AC Drive Control
MVX9000 User Manual 5-35
Descriptions of 
Parameter Settings
50.15
Deceleration Time 2 Range: 0.01 to 600.00 seconds  Default: 10s
Unit: 0.01 seconds
These parameters may be set during operation.
50.12: This parameter sets the time required for the AC drive 
to ramp from 0 Hz to its Maximum Output Frequency (50.04). 
The rate is linear unless S-Curve is “Enabled.” 
50.13: This parameter sets the time required for the AC drive 
to decelerate from the Maximum Output Frequency (50.04) 
down to 0 Hz. The rate is linear unless S-Curve is “Enabled.” 
The second acceleration and deceleration times (50.14 and 
50.15) are identical to the standard acceleration and 
deceleration times (50.12 and 50.13). The second acceleration 
and deceleration times are used only when a Digital input 
terminal is programmed to select between times 1 and 2 
(Refer to 30.12 to 30.15) or when a frequency other than 0 is 
set in parameters 50.16 and 50.17.
In Figure 5-37, the acceleration and deceleration times of the AC 
drive are between 0 Hz and Maximum Output Frequency (50.04). 
If the Maximum Output Frequency is 60 Hz, Minimum Output 
Frequency (50.09) is 1.0 Hz, and acceleration and deceleration 
times are set to 10 seconds. The actual time for the AC drive to 
accelerate from start-up to 60 Hz is 9.83 seconds and the 
deceleration time is also 9.83 seconds. Remember the drive 
always starts timing from 0 Hz. 
Figure 5-37: Acceleration and Deceleration Times
50.16
Transition Point for
Acceleration Time 1 to 2
Range: Default: 0.0
0.0 Disabled
0.1 to 400 Hz Enabled
Max. Output
Frequency 50.04
Time
Frequency
Acceleration
Time
50.12 or 50.14
Deceleration
Time
50.13 or 50.15