Group 30 — Inputs
5-10 MVX9000 User Manual
Descriptions of
Parameter Settings
Example 2:
This example shows a 10 Hz positive offset with full use of the 0 – 10V analog
input or potentiometer scale. A 0V input = 10 Hz and 10V input = maximum
output frequency.
Calculation of Potentiometer Slope
30.09=(1-30.07) x 100% = 83.3%
Figure 5-7: 10 Hz Positive Offset
Defaults:
20.07=60Hz Maximum Output Frequency
30.07=16.7% (10hz/60hz) x 100=Potentiometer Offset
30.08=0 Bias polarity
30.09=83.3% Potentiometer Slope
30.10=0 Potentiometer Direction
Hz
0V
10V
35
0
60
Potentiometer Scale
Max.
Output
Freq.
Bias Adjustment
(20.07)
60 Hz
10V
20 mA
5V
12 mA
0V
4 mA
0 Hz
10 Hz