Group 50 — AC Drive Control
MVX9000 User Manual 5-37
Descriptions of
Parameter Settings
50.20
Jog Acceleration /
Deceleration Time
Range: 0.01 to 600.00 seconds Default: 1.00 sec
Unit: 0.01 seconds
This parameter sets the acceleration and deceleration time for
the Jog operation.
50.21
Jog Frequency Range: 0.1 to 400.0 Hz Default: 6.0 Hz
Unit: 0.1 Hz
This parameter may be set during operation.
Figure 5-39: Jog Frequency
50.22
Reverse Operation
Enable
Range: Default: 00
00 enable REV operation
01 disable REV operation
This parameter enables the AC Motor Drive’s ability to
operate in the reverse direction.
Jog
Frequency
50.21
Time
Frequency
Acceleration
Time
50.20
Deceleration
Time
50.20
Jog Operation
Command
ON
OFF