Fuses and Circuit Breakers
4-8 MVX9000 User Manual
Start-Up
Procedures
Table 4-2: Fuse Specification Chart (Continued)
Table 4-3: Heat Loss Data
When mounting the MVX9000 in an enclosure the following inverter heat loss
should be considered. Failure to provide adequate cooling may cause premature
failure of the inverter and/or overtemperature faults.
Model
Input
Current
(A)
Output
Current
(A)
Line Fuse
MMP Catalog
Number
Recommended
Contactor
Catalog NumberI(A) Buss
005A0-4 8.5 8.2 30 JJS-30 XTPR016BC1 XTCE018C_
007A0-4 14 13 50 JJS-50 XTPR016BC1 XTCE025C_
010A0-4 23 18 70 JJS-70 XTPR025BC1 XTCE025C_
001A0-5 2.4 1.7 5 JJS-6 XTPR6P3BC1 XTCE007B_
002A0-5 4.2 3.0 10 JJS-10 XTPR6P3BC1 XTCE007B_
003A0-5 5.9 4.2 15 JJS-15 XTPR6P3BC1 XTCE007B_
005A0-5 7.0 6.6 15 JJS-15 XTPR010BC1 XTCE007B_
007A0-5 10.5 9.9 20 JJS-20 XTPR012BC1 XTCE012B_
010A0-5 12.9 12.2 30 JJS-
30 XTPR016BC1 XTCE015B_
Model
Watts Lost
at 9 kHz Model
Watts Lost
at 9 kHz
Watts Lost
at 6 kHz
MVXF25A0-1 (1-phase) 20 MVX001A0-4 38
MVXF50A0-1 (1-phase) 20 MVX002A0-4 75
MVX001A0-1 (1-phase) 38 MVX003A0-4 110
MVXF50A0-2 (1-phase) 20 MVX005A0-4 185
MVXF50A0-2 (3-phase) 20 MVX007A0-4 275
MVX001A0-2 (1-phase) 38 MVX010A0-4 375
MVX001A0-2 (3-phase) 38 MVX001A0-5 30
MVX002A0-2 (1-phase) 75 MVX002A0-5 58
MVX002A0-2 (3-phase) 75 MVX003A0-5 83
MVX003A0-2 (1-phase) 110 MVX005A0-5 132
MVX003A0-2 (3-phase) 110 MVX007A0-5 191
MVX005A0-2 185 MVX010A0-5 211
MVX007A0-2 275