Fuses and Circuit Breakers
MVX9000 User Manual 4-9
Start-Up
Procedures
Wiring the Inverter to Incoming Power
Step 6: In this step, connect the wiring to the input of the inverter. First determine
whether the inverter model requires three-phase power only, or if it can accept
either singe-phase or three-phase power. All models have the same power
connector terminals labeled L1, L2, L3 and (Ground). Refer to the specifications
label (on the side of the inverter) for the acceptable power source types! For
inverters which can accept single-phase power, use terminals L1 and L2.
CAUTION!
Be sure that the input voltage matches the inverter specifications:
• Single-phase 100 to 120V 50/60 Hz
• Single-/Three-phase 200 to 240V 50/60 Hz (up to 2.2 kW)
• Three-phase 200 to 230V 50/60 Hz (above 2.2 kW)
• Three-phase 380 to 460V 50/60 Hz
• Three-phase 500 to 600V 50/60 Hz
CAUTION!
Be sure not to connect an AC power supply
to the output terminals. Otherwise, there is
the danger of injury and/or fire.
Note:
L1, L2, L3: Three-phase 200 to 230V 50/60 Hz
Three-phase 380 to 460V 50/60 Hz
Three-phase 500 to 600V 50/60 Hz
Any two inputs:
Single-phase 100 to 120V 50/60 Hz;
Single-phase 200 to 240V 50/60 Hz
Power Input
L3L2L1
T3
T2T1
Power Output